Pulsafeeder Pulsar DLCM Manual do Utilizador Página 1

Consulte online ou descarregue Manual do Utilizador para Bombas Pulsafeeder Pulsar DLCM. Pulsafeeder Pulsar DLCM User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 135
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
INSTALLATION
OPERATION
MAINTENANCE
INSTRUCTION
BULLETIN No. IOM-PS-DLCM-1101-Rev E
Manufacturer’s of Quality Pumps,
Controls and Systems
Engineered Pump Operations
2883 Brighton-Henrietta Townline Road
Rochester, New York 14623
Telephone: (585) 292-8000 Fax: (585) 424-5619
http://www.pulsa.com
Vista de página 0
1 2 3 4 5 6 ... 134 135

Resumo do Conteúdo

Página 1 - INSTRUCTION

INSTALLATIONOPERATIONMAINTENANCEINSTRUCTIONBULLETIN No. IOM-PS-DLCM-1101-Rev EManufacturer’s of Quality Pumps,Controls and SystemsEngineered Pump Oper

Página 2 - FCC Warning

43. Equipment InspectionWhen you receive your order, check all equipment for:i Completeness against the shipping document / purchase orderi For any e

Página 3 - Table of Contents

9411. Trouble Shooting Guide11.1 System DiagnosticsYour DLCM contains extensive diagnostics that allow it to determine the source of common problems

Página 4

95MENU (DIAGNOSTICS) [cont]Symptom Probable Cause Possible SolutionDIAG 7/11DRIVE TEMP:FAILThe DLCM internal temperature hasexceeded the rating.Re-loc

Página 5 - IAGNOSTIC

96PULSAR DC MOTORSymptom Probable Cause Possible SolutionMotor will not start. No power supplied. Check power source to DLCM.. Motor wired incorrectly

Página 6 - Conventions

97ANALOG INPUTSymptom Probable Cause Possible SolutionInput wired incorrectly. Check wiring.Input not wired to correct channel. Refer to Section 5 – I

Página 7 - 1. Introduction

98ALARM RELAY OUTPUT (Low Voltage J5)Symptom Probable Cause Possible SolutionNo Output Output wired incorrectly. Check wiring.External Device not pow

Página 8 - 1.4 Accessories

99UNITSSymptom Probable Cause Possible SolutionUnits do notincrement withchange in %.Unit not properly calibrated. Calibrationbeyond display resoluti

Página 9 - 2. Safety Considerations

100Failed to detect shaft rotation with themotor turned onThe tachometer has failed. Remove power tothe DLCM and pump motor. Turn the powerback on a

Página 10 - 4. Storage Instructions

101ENCODER ERRORSymptom Probable Cause Possible SolutionEncoder defective. Contact Technical ServicesBroken or jammed gears – contact TechnicalService

Página 11 - 5. Installation

10211.1.2 Tachometer TroubleshootingThe DLCM utilizes the Tachometer sensor installed in the gear box to determine motor speed. Thissensor detects t

Página 12 - 5.3 Electrical Wiring

10316. Slowly rotate the pump motor observing the high and low multi-meter readings. The output shouldnow transition from a value below 0.35VDC when

Página 13 - 5.3.1 Getting Started

55. Installation5.1 LocationReview the Safety section prior to installing the DLCM. It contains information required to properlyinstall and operate

Página 14 - Figure 3. Field Wiring Board

10412. Conversion (Manual to DLCM)Your PULSAR can be easily converted from a Manual Stroke Adjustment Mechanism to the DLCM. TheDLCM effectively re

Página 15 - 5.4 High Voltage Connections

105Figure 25 – DLCM/Eccentric mating components7. Locate the face on the bottom of the DLCM that mates with the face of the lip of the eccentric box.

Página 16

10613. General RepairsThe DLCM contains no user-serviceable components within its main enclosure. In the un-likely event thatyour DLCM needs to be r

Página 17 - 5.4.2 PULSAR Motor

10713.2 DLCM Replacement The following procedure assumes that you have received your replacement DLCM and are ready toperform the replacement.1. If

Página 18 - 5.4.3 Alarm Relay

1085. Remove the Tachometer Sensor Input Cable on the Field Wiring Board.a) Disconnect the wire (typically brown) connected to Pin 1 of J10.b) Disco

Página 19 - 5.5.1 Analog Inputs

1097. Remove the four screws and Teflon Gaskets that retain the conduit adapter(refer to Figure 28).Figure 28 – Conduit Adapter Screw RemovalWhen remo

Página 20 - 5.5.2 Alarm Input

11012. Note the position of the PULSAR adjustment shaft 'flats'. They mate with a slot in the DLCM drivecoupling of the output shaft. The

Página 21

11114. Orient the DLCM properly at a comfortable height above the pump and align the slot in the DLCMcoupling with the 'flats' on the adjust

Página 22 - 5.6.1 Current Output

112Figure 33 – Shaft Alignment

Página 23 - 5.7 Tachometer Input

11316. Align the Conduit Adapter with the mating surface on the DLCM. A card edge in the DLCM housing will mate with an edge connector on the Conduit

Página 24

6AVOID LOCATIONS WHERE THE DLCM WOULD BE SUBJECTED TO EXTREME COLD OR HEAT[LESS THAN –18° CELSIUS (0° FAHRENHEIT) OR GREATER THAN 40 ° CELSIUS (104 °F

Página 25 - 5.8 Motor Thermostat

11414. PulsaNet SpecificationFor simplicity, the DLC, DLCM, MLC, MLCM, NEMA-4X and NEMA-7 variations will ALL be referredto as the DLC unless otherwi

Página 26 - Important Wiring Detail

11514.3 MODBUS MessagingThe MODBUS protocol was written for use with PLC’s. Programmable Logic Controllers (PLC’s)typically have relay outputs, digi

Página 27 - 5.10 Fuse Replacement

11614.5 CoilsCoils are discrete, single bit outputs like the ALARM OUTPUT and DIGITAL OUTPUT.Notes:i Read only.i The coil information is packed as 8

Página 28 - 6. Start Up Instructions

11714.7 Input RegistersThese 16-bit input registers contain Analog (4-20mA) and Thermistor input readings.Notes: i The input information is returned a

Página 29 - 6.1.1.2 Keypad:

118Function Address DDE Ref. Purpose Data FormatRead (0x03) 0x0008 400009 Screen Character: Row 1, Column 9 Word (0x0 – 0xFFFF) [Note #1]Read (0x03)

Página 30

119Function Address DDE Ref. Purpose Data FormatRead (0x03) 0x003A 400059 Flash Character: Row 2, Column 11 Word (0x0 – 0xFFFF) [Note #1]Read (0x03)

Página 31

120Notes:1. There is one character per 16-bit value, which resides in the least significant byte.2. The most significant byte contains the cursor st

Página 32

12112. Reading returns the current condition from RAM that can be either 0=Security Off, 1=Tamper Proof,2=Calibration Settings. Writing while securit

Página 33 - 6.1.6 Test Pump Motor

122SUPPORTED FUNCTION CODES and SUB-FUNCTION CODES0x01 READ COIL STATUS (bits) SUPPORTED0x02 READ INPUT STATUS (bits). SUPPORTED0x03 READ HOLDING REGI

Página 34 - 6.1.7 Set Time and Date

12315. MODBUS Mode15.1 IntroductionThe serial communications supplied with the DLC/M is similar in operation to that with the 4-20mAsignal. The [MO

Página 35

75.3.1 Getting StartedThe field wiring of the DLCM is accomplished through a rear access cover at the back of the unit –near the PULSAR gearbox and mo

Página 36

12416. Spare PartsUser replaceable parts for the DLCM.Table 4: Miscellaneous Replacement PartsPulsafeeder P/N Description QtyNP250012-000 Clear Lexa

Página 37 - 6.2 Wrapping up

125Diagnostic FormPulsafeeder, Inc.2883 Brighton-Henrietta TL RoadRochester, New York, 14623 Attn: Technical ServicesTelephone (585) 292-8000 Fax (585

Página 38 - 7. General Operation

126(Page 1 of 2)What area did the problem fall into: (Refer to Bulletin No. IOM-PS-DLCM-1101-Rev E, Section 11 – Trouble Shooting Guide) Check the one

Página 39

127(Page 2 of 2)

Página 41

BULLETIN No. IOM-PS-DLCM-1101-Rev EEngineered Pump Operations2883 Brighton-Henrietta Townline RoadRochester, New York 14623Telephone: (585) 292-800

Página 42

85.3.2 Finding your way around the Field Wiring BoardThe electrical connections are segregated on the Field Wiring Board. The high voltage connection

Página 43

95.4 High Voltage ConnectionsThere are only three high voltage connections to be made on the DLCM: supply power (J1), PULSARmotor load (J3), and Alar

Página 44

10The DLCM with an attached pump motor and alarm load, should be connected to its own branchcircuit. Size the supply wire and protective element acco

Página 45

115.4.2 PULSAR MotorIn most cases the DLCM is supplied with a factory installed DC motor. If a motor was not supplied, itis important to select the p

Página 46

125.4.3 Alarm RelayThe Alarm Relay is an output that is configured by the operator. Refer to Section 7 – GeneralOperation for specific instructions o

Página 47 - 7.2 Menu

135.5.1 Analog InputsThe DLCM can accept either one or two analog input signals. These signals ultimately control thepump’s flow. Analog Input #1 is

Página 48

iiDLCM™ FACTORY SERVICE POLICYYour DLCM is a state of the art microprocessor based stroke length and motor speed control for use withPULSAR Diaphragm

Página 49 - 7.2.2 Diagnostics

145.5.2 Alarm InputThe Alarm Dry Contact Input is designed to operate with the PULSAlarm leak detection option. It issoftware configurable to generat

Página 50

155.6 Low Voltage Output ConnectionsThere are two types of Low Voltage outputs: Analog (e.g., 4-20mA) and Transistor based Dry Contact.The Low Voltag

Página 51 - 7.2.3 Set Time and Date

165.6.1 Current OutputThe Current Output Channel can follow one of three signals:a) Calibrated flowb) Calibrated stroke lengthc) True motor speedIt

Página 52

175.6.3 Run Status or Stroke CounterThe Status output can be configured through software to indicate that the pump motor is on or togenerate a pulse w

Página 53

18Figure 8 – Tachometer and Pump Motor Thermostat ConnectionsTo connect the Tachometer Input, connect the wire labeled VDC (typically brown) to the co

Página 54

195.8 Motor ThermostatThe motor thermostat has been supplied as an equipment safety measure. This allows the DLCM pumpmotor to operate without the d

Página 55

20Important Wiring DetailSlave to SlaveWhen connecting two Slaves, the wiring is straight through. For example: Connect the transmit linesto the tra

Página 56

215.10 Fuse ReplacementAlthough Fuse replacement is not a part of normal installation, it is possible that fuse failure will resultfrom improper wiri

Página 57

226. Start Up Instructions6.1 OverviewOnce all electrical connections have been made, your DLCM is ready for Start-up. The following ninesections

Página 58 - Go To Default

236.1.1.1 Display: This is a 2 line by 16 character alpha-numeric Liquid Crystal Display (LCD) located above thekeypad. It is back-lit with a yello

Página 59 - 7.2.6 Analog Output Set Up

iiiTable of Contents1. INTRODUCTION...

Página 60 - 7.2.7 Motor Speed Display

246.1.1.3 Manual Adjustment Knob:The manual adjustment knob is mechanically attached to the PULSAR stroke length adjustmentmechanism. The DLCM uses

Página 61 - 7.2.8 End Point Set Up

256.1.3 Confirm Correct Incoming PowerDouble check that the wiring access cover is on and tightened down. Whenever power is supplied tothe DLCM, the

Página 62 - 7.2.8.1 End Point Example

26The keypad can be tested by depressing each key separately. Most, but not all keys will cause the texton the display to change. Do not be alarmed

Página 63

27 Menu Factory Re-initialization:Use this procedure if the display and key pad appear to be functioning properly, but you suspect otherproblems with

Página 64

286.1.7 Set Time and DateThe clock on your DLCM has been activated at the factory, but you should set it to the local time anddate of the installation

Página 65

296.1.8 Flow Calibration (1-point).Your DLCM is factory calibrated at rated flow and pressure (1-point). Nevertheless, you shouldalways perform a cal

Página 66

3014. Pressing [ENTER] on the last position will cause the {CONFIRM CHANGE? / YES} screen to bedisplayed. Press [ENTER] to accept. Your 1-point cali

Página 67

316. When the displayed value stabilizes, press [ENTER] to accept it. The {INPUT ANALOG MAX /100% = XXmA} screen is displayed. Adjust your PLC to ou

Página 68 - 7.2.11 Digital Output Set Up

327. General OperationThis section covers the General Operation of the DLCM as it relates to software. It includes detailedinstructions and example

Página 69

33You can "skip" a calibration point by entering a flow value of 0.0000. “Skipping” a point means thatit will be omitted from the mathemati

Página 70

iv7.2 Menu ...41

Página 71 - DANGEROUS OPERATION

3410. When you are ready, press [ENTER], which will start the pump motor for a period of 60 seconds. Thescreen will show a 60 second timer and displa

Página 72 - Selection Action

35 Change Constants Procedure1. Navigate to the Change Constants menu by pressing [CAL]. The {CALIBRATE / PUMP FLOW}menu is displayed. Press [ENTE

Página 73 - 7.2.16 Analog Mode

36TUNE FLOW 60.0%0.1000 GUsing [UP] or [DOWN] enter the volume displaced for 1 minute of pump flow at the current motorspeed and stroke length. The

Página 74

37Send the low analog signal to the DLCM (i.e., 0mA, 1mA, 4mA or 1 volt input to the J4 Current 1terminals) from the signal generating device (e.g., P

Página 75 - 7.2.17 MODBUS Mode

387.1.2.2 Analog Input #2 CalibrationThe following is a minimal procedure for calibrating Analog Input #2 if the 2 – Signals option is to beused. In

Página 76

396. You are now ready to set the Signal Ratio. This option allows you to scale the Analog signal input tothe pump output. Use this option only if y

Página 77

407.1.4 Analog Output Signal CalibrationDepending upon the option selected, {STROKE & SPEED} or {STROKE POSITION} or {MOTORSPEED}, the DLCM will g

Página 78 - 7.2.18 Security

417.2 MenuThe default values of the DLCM Controller have been factory set, but you may want to configure theDLCM to meet your specific application.Th

Página 79 - 7.2.19 Number Format

427.2.1 Alarm, and Error messagesWhen an error occurs, the DLCM flashes Alarm and Error messages alternately with the standarddisplay. If the error i

Página 80 - 7.2.21 Serial Communications

437.2.2 DiagnosticsThe DLCM is supplied with a complete diagnostic menu. It will alert you if something has failed, thetime and date of the failure,

Página 81

vDIAGNOSTIC FORM...

Página 82

448. Press [UP] to scroll to the next sub-menu. The DLCM is equipped with a thermistor to monitorinternal enclosure temperatures. If the temperatur

Página 83 - 7.2.22 Serial Diagnostics

4512. Press [UP] to scroll to the next sub-menu. The total Stroke count of the pump is displayed here. Toreset the Stroke count, press [ENTER] and y

Página 84

463. The time will now be flashing with the cursor located under the hour position. Press [UP] or [DOWN]to adjust the time to your local time.12 HR

Página 85 - 7.2.23 Language

479. If "AUTO CHANGE" was selected in the previous step, the DLCM prompts you for the current day ofthe week. Press [UP] to scroll through

Página 86 - 7.3 Units

482. The menu for having the DLCM freeze at the last signal is displayed. ANALOG SIG FAILFREEZE @LAST SIGTo accept this action, press [ENTER]. Go to s

Página 87 - 7.6 Batch

49If {MANUAL MODE} is selected, the DLCM will enter the manual mode as soon as the signal loss isdetected. It will remain in Manual Mode until it is

Página 88 - 7.6.3 Overlapped

505. The {ERROR MESSAGE / ENABLED} screen is displayed. ERROR MESSAGEENABLEDTo accept this value, press [ENTER] and the {–MENU– / ANALOG SIG FAIL} scr

Página 89

51Here are some general guide lines:− Increase this value as you increase the number of nodes on the network.− Increase this value as you decrease t

Página 90

52c) Go To Default

Página 91 - 6:54a 2/4/01

53Press [UP] or [DOWN] to select the desired option.MODBUS FAIL #XFREEZE @LAST SIGPress[UP]MODBUS FAIL #XMOTOR OFFPress[UP]MODBUS FAIL #XGO TO DEFA

Página 92

viConventionsFor the remainder of this bulletin, the following Conventions are in effect.A WARNING DEFINES A CONDITION THAT COULD CAUSE DAMAGE TO BOTH

Página 93

54The STROKE & SPEED output actually represents Calibrated Flow where 0% flow may notcorrelate to 0% stroke position.Press [ENTER] to accept this

Página 94 - 9. Specifications

557.2.8 End Point Set UpThe End Point Set Up menu is a powerful tool that allows you to modify the performance of yourDLCM. The term 'End Points

Página 95 - Low Voltage Outputs

56At the 100% Adjustment (maximum value on the x-axis), the DLCM is operating at 100% strokelength and 100% motor speed. This results in a 100% flow

Página 96 - Control Inputs

57Figure 15 – Typical End Point ExampleA better way to accomplish this is to modify the Maximum End Point for Stroke Length. If we changethe Maximum

Página 97 - 10. Factory Default Values

58 End Point Set Up procedure1. Press [MENU] to enter the {–MENU–} sub-system. Press [UP] or [DOWN] until {–MENU– / ENDPOINT} is displayed. 2. Pre

Página 98

59The leak sensor switch must be a dry contacting type. Refer to Section 5-Installation: Low VoltageInputs for wiring information.If you select the &

Página 99

60The level sensor or Start/Stop switch must be a dry contacting type. Refer to Section 5-Installation:Low Voltage Input Connections.If you select th

Página 100 - 11. Trouble Shooting Guide

6110. If you want the PULSAR motor to stay on when a Drum Level is sensed, press [UP] to scroll to{NO}.and press [ENTER].LEVEL SWITCHMOTOR OFF? NO11

Página 101

627.2.11 Digital Output Set UpThis sub-menu allows you to determine if the Digital Output is to be used as a counter for pumpstrokes, as a remote mot

Página 102

63 Digital Output Set Up Procedure1. Press [MENU] once and then press [UP] or [DOWN] until the display reads {–MENU– / DIGITALOUTPUT}.–MENU–DIGITAL

Página 103

11. IntroductionThe DLCM is an advanced microprocessor based controller designed for use with the PULSAR diaphragmmetering pump. It controls the out

Página 104

647.2.12 Motor Thermostat Set UpThis sub-menu allows you to configure the DLCM to interact with the pump motor thermostat.Depending on the applicatio

Página 105

655. The {MOTOR THERMOSTAT / ALARM RELAY? YES} screen is displayed.MOTOR THERMOSTATALARM RELAY? YESPress [UP] to select between {YES} and {NO}.MOTOR

Página 106

667.2.14 Power Failure Set UpThis sub-menu allows you to configure the way the DLCM reacts when power is restored after a poweroutage. Additionally

Página 107 - 11.1.1 Encoder Diagnostics

677.2.15 Alarm Relay This sub-menu sets up the alarm relay outputs as normally open or normally closed.These screens configure both the high voltage

Página 108

68 Analog Mode Set Up Procedure1. Press [MENU] once and then [UP] or [DOWN] until the screen {–MENU– / ANALOG MODE} isdisplayed.-MENU-ANALOG MODEPre

Página 109

69Press [UP] or [DOWN] to set the {#1 SAMPLE SIZE}. The ‘#1’ refers to the signal that controls theSTROKE adjustment.Increase the number of samples t

Página 110

70 MODBUS mode setup procedure:1. Press [MENU]. Press [UP] or [DOWN] until the {–MENU– / MODBUS MODE} screen is displayed.–MENU-MODBUS MODEPress [E

Página 111

717.2.17.2 {STROKE & SPEED / 2 – SIGNALS} Setup8. With the {STROKE & SPEED / 1 – SIGNAL} screen displayed (refer to step 3), press [UP] to d

Página 112 - 13. General Repairs

727.2.18 SecurityThe DLCM has three modes of security:− None (OFF)− Tamper Proof− CalibrationWith Tamper Proof security active, the DLCM will lockou

Página 113 - 13.2 DLCM Replacement

737. If the pin number is not correct or you don’t want the selected security level, press [UP] to change thedisplay to {CONFIRM CHANGE? / NO}CONFIRM

Página 114

21.2 DLCM Standard Featuresi DC Motor Speed Control with tachometer feedbacki Manual Stroke Length Controli Keypadi Back-lit 2 line 16 character LCD

Página 115

747.2.20 Contrast AdjustThe DLCM display contrast can be adjusted to a desired setting. Contrast Adjustment Procedure1. Press [MENU]. Press [UP] o

Página 116

75If you are installing this DLCM into an existing network, retrieve the following parameters (boldindicates default DLCM values not network defaults)

Página 117

76Press [UP] or [DOWN] to set the parity type. DATA PARITYEVENPress[UP]DATA PARITYODDPress[UP]DATA PARITYNONEPress [ENTER] to accept.6. The Class se

Página 118 - Figure 33 – Shaft Alignment

77To set or view Slaves manually, press [UP] or [DOWN]. As you do so, the display will show theaddress followed by the status,IDENTIFY SLAVES1

Página 119

787.2.22.1 Loopback Test ProcedureThe Loopback test is helpful in the identification of wiring errors. While this menu is displayed theDLCM transmit

Página 120 - 14. PulsaNet Specification

797.2.23 Language All displayed text can be displayed in English, Spanish, French or German. Language Set Up Procedure1. Press [MENU]. Press [UP]

Página 121 - 14.3 MODBUS Messaging

80Press [UP] to change the value to {YES}. Press [ENTER] to accept your selection. The followingmessage is displayed:PLEASE WAIT5. The first screen

Página 122 - 14.5 Coils

817.4 Varying the Flow Rate - ManuallyWhen the DLCM is in Manual Mode, pump flow rate can be increased by pressing [UP]. The flow rate isdecreased by

Página 123 - Holding Registers

827.6.2 RepeatingA Repeating Batch will start at a specified time and run for a specified duration. It will stop for aspecified period of time and th

Página 124

83 Batching system Set Up procedure:1. Press [BATCH], to enter the batch set-up menu.2. The display will come up as {BATCHES / ACTIVE} or {BATCHES

Página 125

32. Safety ConsiderationsThe DLCM is a sophisticated microprocessor based controller for use only with PULSAR diaphragmmetering pumps. It yields tre

Página 126

847. The cursor then moves to minutes field. Use [UP] or [DOWN] to scroll through the numbers 0-5. Setthe first digit of the minute value one positi

Página 127

8516. When the batch has operated for the specified time period, it will automatically shut off the pump'smotor. 17. If this a One Time Only batc

Página 128

868. Diagrams: Installation / ComponentDIAGRAM 1 – DLCM Wiring Diagram

Página 129 - 15. MODBUS Mode

87Diagram 2 – Serial Communications – RS 485 Connections

Página 130 - 16. Spare Parts

889. Specifications9.1 OverviewThe DLCM controller for Pulsar Pumps is an upgrade from the DLC stroke length controller, whichprovides all of the sa

Página 131 - Diagnostic Form

89Low Voltage Inputs (cont)Inputs Field WiringLocationSpecification / DescriptionPULSAlarm(Leak Detection)J4 Pin 3 is +J4 Pin 4 is –Dry Contact. (Opti

Página 132 - (Page 1 of 2)

90High Voltage Inputs Inputs Field WiringLocationSpecification / DescriptionLine Power:J1 Factory configured to one of the following:115VAC ±10%, 50/6

Página 133 - Page 2 of 2

9110. Factory Default ValuesCALIBRATIONPump Flow 1-Point Calibration on PULSAR at Rated Flow and Pressure.Analog Input 4.0 - 20.0mA @ 100% RatioAnalo

Página 134

92NUMBER FORMATSeparators X , XXX . XX (Comma / Decimal)Position PULSAR dependent (e.g., 9.99999, 0.999999, etc.)Factory set to match pumphead size.

Página 135 - Rochester, New York 14623

93FACTORY DECIMAL POSITION SETTINGS (cont.)RATED CAPACITY RANGE UNITS –MENU – / DECIMAL POSITION0.00599999 to 0.0599999 CMH 0.9999991.58503 to 15.8503

Comentários a estes Manuais

Sem comentários